In a fire alarm, comfort no longer calls the shots – safety does, and that's handled by a certified system that must not depend on anything else. The shading still has a role to play: it should get out of the way for clear sightlines and access, in a way that's predictable and can't be disturbed by an ordinary command. Here's how that's built.
What happens when the alarm goes off
SOLO receives an alarm command and raises the shade. It then locks: the fabric can't be lowered again until the alarm is reset – not from the app, not from the keypad, not remotely. The lock lives in the unit itself, so it holds even if the network or the cloud is down (see How secure is connected solar shading?).
EN 54 separates the core from what's connected to it
EN 54 is the standard for fire detection and fire alarm systems. It separates the fire alarm system itself – detectors, control panel, alarm devices – from the other systems in the building that an alarm can command, such as doors, ventilation or shading. The shading belongs to the latter group.
That's an important line to keep in mind: SOLO is not part of the certified fire alarm system, and the building's fire safety doesn't rest on the shading. The function is a connected measure – a useful addition for clear sightlines and access – not a substitute for anything in the fire safety design.
Two ways in: RS-485 or MQTT
The alarm signal can arrive in two ways. RS-485 is a wired, serial bus – robust, with no dependency on a network. MQTT is network-based and fits when the fire alarm installation already talks to other systems over IP. You choose one path, or both, based on what the installation already offers.
Why the lock matters
An alarm stays active until someone deliberately resets it – not until someone happens to press the wrong thing. That's why the shading isn't lowered by accident in the middle of an evacuation, by a tap in the app, a button press or a remote command. The lock lives in the unit, not in the cloud or the network, for the same reason as everything else in SOLO's basic design: the function that has to hold can't depend on anything else being connected.
Commissioning: a shared task
The fire-alarm function is planned together with your fire safety officer and based on the fire alarm installation's intended interface – which signal it gives, which zones it covers and how reset should work. It isn't something SOLO decides on its own.
To see how it lands for your building, go through the configuration tool together with your fire safety officer.